Diagnosis Kondisi Minyak Tranformator Menggunakan Teknik Dissolved Gas Analysis
DOI:
https://doi.org/10.55893/jt.vol21no1.428Keywords:
Transformer Oil, Dissolved Gas Analysis, Breakdown VoltageAbstract
At the Cikalong hydropower plant there are 3 power transformers with a voltage rating of 6.3/77 kV, because of their long life, it is necessary to analyze the condition of the transformer oil. One way to determine the level of fault gas contained in transformer oil is the DGA (Dissolved Gas Analysis) test. DGA will extract the gas to find out indications of disturbance based on the interpretation of the dissolved gases data, namely the Total Dissolved Combustible Gas (TDCG), Key Gas, Roger's Ratio, Doernenberg's Ratio and Duval's Triangle methods. This method is in order to determine the condition of the transformer oil is normal or not, measure the breakdown voltage value and calculate the correlation value between operating hours and the amount of power production. The results of the DGA analysis on transformer units 1, 2, and 3 of the Cikalong hydropower sub-unit show the TDCG value in condition 1, which includes all transformers in good condition. The value of the correlation coefficient between hours of operation and the number of kWh production with TDCG is 0.267 and 0.297, respectively, which indicates the relationship between these variables is a weak relationship (standard value is close to 1).
References
A Dedi Roi Candra Sihombing, “Analisa Kondisi Minyak Isolasi Transformator Berdasarkan Pengujian DGA Pada Transformator 3 150/20 kV 60 MVA PT. PLN (Persero) Gardu Induk Cibatu” 2020.
A. R. Demmassabu, L. S. Patras, F. Lisi, “Analisis Kegagalan Transformator Daya Berdasarkan Hasil Uji Dengan Metode TDCG, Key Gas, Roger's Ratio, Duval's Triangle Pada Gardu Induk” eJurnal Teknik Elektro dan Komputer, ISSN : 2301-8402. 2014.
Faris Aljiddi, “Analisis Hasil Uji DGA untuk Memprediksi Rentang Waktu Purifikasi Minyak Transformator dengan Metode TDCG dan Roger’s Ratio” 2019.
Haz, F. and Aditya, I. (2020) ‘Analisis Setting Proteksi Relai Arus Lebih dan Relai Gangguan Tanah Pada Transformator Daya 60 MVA di Gardu Induk 150 kV Cibatu’, Journal of Electrical Engineering and Information Technology
Hidayat, M. R. et al. (2020) ‘Analisis Kemampuan Minyak Isolasi Transformator Daya Merek Unindo Dengan Pengujian Dissolved Gas Analysis dan Breakdown Voltage di Gardu Induk Serpong’, EPSILON: Journal of Electrical Engineering and Information, pp. 100–106.Pramono, A., Haddin, M. and Nugroho, D. (2016) ‘Analisis Minyak Transformator Daya Berdasarkan Dissolved Gas Analysis (Dga) Menggunakan Data Mining Dengan Algoritma J48’, Telematika, 9(2), p. 78. doi: 10.35671/telematika.v9i2.457.
IEEE std. C57.104-2008, IEEE Guide for Dissolved Gas Analysis in Transformer. 2008.
P, A. Y. C., Taqiyyudin, M. A. and Basuki, B. M. (2018) ‘Analisis Kegagalan Transformator Berdasarkan Hasil Pengujian Dissolved’.
Rahmat Hardityo, “Deteksi dan Analisis Indikasi Kegagalan Transformator Dengan Metode Analisis Gas Terlarut” 2008.
Suardi Yakub, Modul Panduan Belajar Statistik Probabilitas. 2012.
Syakur, A. and Lazuardi, W. (2019) ‘Penerapan Metode Interpretasi Rasio Roger , Segitiga Duval , Breakdown Test , dan Water Content Test untuk Diagnosis Kelayakan Minyak Transformator’, Teknik, 40(1), pp. 63–68. doi: 10.14710/teknik.v40n1.22056.Iskandar, H. R. (2021) ‘Studi Kelayakan Operasi Berdasarkan Uji Dissolve Gas Analysis pada Transformator Distribusi 150 kV Gardu Induk Cibabat Cimahi’, Kilat, 10(1), pp. 10–21. doi: 10.33322/kilat.v10i1.963.
Additional Files
Published
Issue
Section
License
Copyright (c) 2022 Fauzia Haz, Muhammad Rizki Akbar, Giri Angga Setia

This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License.
Penulis yang menyerahkan artikel di Jurnal Teknik: Media Pengembangan dan Aplikasi Teknik untuk keperluan publikasi telah mengetahui bahwa Jurnal Teknik: Media Pengembangan dan Aplikasi Teknik memberikan akses terbuka terhadap konten untuk mendukung pertukaran informasi mengenai ilmu pengetahuan, sesuai dengan penerbitan daring yang berbasis Open Access Journal dan mengikuti Creative Commons Attribution 4.0 International License. Sehingga penulis setuju dengan ketentuan-ketentuan berikut:
1. Penulis memegang hak cipta dan memberikan hak publikasi pertama kepada pihak jurnal dengan pekerjaan secara bersamaan
di bawah Creative Commons Attribution 4.0 International License yang memungkinkan orang lain untuk berbagi pekerjaan
dengan pengakuan kepengarangan karya dan publikasi pertama artikel tersebut di Jurnal Teknik: Media Pengembangan dan
Aplikasi Teknik.
2. Penulis dapat melakukan perjanjian tambahan untuk hak distribusi non-eksklusif artikel yang telah diterbitkan di jurnal ini
(misalnya, posting ke sebuah repositori institusi atau menerbitkannya dalam sebuah buku), dengan mengakui bahwa
publikasi pertama dilakukan di Jurnal Teknik: Media Pengembangan dan Aplikasi Teknik.
3. Penulis diizinkan dan didorong untuk menyebarkan karya mereka secara daring (misalnya, dalam repositori institusi atau
laman web penulis) setelah artikel terbit (proses penerbitan artikel selesai). Hal ini terkait dengan imbas dari pertukaran
informasi yang produktif (Lihat Pengaruh Open Access).