Reliability Index Assessment-Section Technique pada Distribusi Listrik Penyulang Suci Menggunakan Software ETAP
DOI:
https://doi.org/10.55893/jt.vol23no1.528Keywords:
Electrical Distribution, ETAP, Reliability Index, RIA-section techniqueAbstract
Problems that often occur with electricity distribution network quality, continuity and availability services consumers. Study aims evaluate reliability of the 20 kV medium-voltage electricity distribution system at the Suci ULP Garut Kota feeder, where 2021 Suci feeder experienced 14 disturbances duration 791 minutes (13.1 hours), including a medium-voltage overhead line that broke 2 Phase. Determining the reliability index value electricity distribution system of the Kudus ULP Garut City feeder, mathematical calculations were carried out using RIA-section technique predetermined formula and simulated using ETAP software with study case reliability assessment. Based on the results of the study, improvement was made that the reliability value feeder was stable. Repairs were carried out 2 times, first repair, 2 fuse cutouts were installed and 4 transformers were moved, while the second repair was to divide the Suci feeder into 2 parts, namely the western Suci feeder and the eastern Suci feeder. So making these improvements the reliability index Suci feeder becomes stable and meets what has been SPLN 68-2: 1986, which is below SAIFI 3.3 times/customer/year and SAIDI 21.9 hours/customer/year.
References
Budi, G. P., Gandi, A., Keandalan, A., Distribusi…, S., Putu, G., Arigandi, B., Hartati, R. S., & Weking, A. I. (2015). ANALISA KEANDALAN SISTEM DISTRIBUSI PENYULANG KAMPUS DENGAN MENGGUNAKAN PENGGABUNGAN METODE SECTION TECKNIQUE DAN RIA. Dalam Teknologi Elektro (Vol. 14, Nomor 2).
Fatoni, A., Seto Wibowo, R., Soeprijanto, A., & Elektro, J. T. (2016). Analisa Keandalan Sistem Distribusi 20 kV PT.PLN Rayon Lumajang dengan Metode FMEA (Failure Modes and Effects Analysis). JURNAL TEKNIK ITS, 5(2).
Hidayatullah, R. (2017). Analisa Keandalan Sistem Distribusi 20KV Menggunakan Metode Section Technique dan Ria-Section Technique pada Penyulang Adi Sucipto Pekanbaru.
Kusuma, W., Joto, R., & Mieftah, M. (2022). Analisis Keandalan Sistem Distribusi 20kV Pada Penyulang Pujon PT. PLN (PERSERO) ULP Batu.
Laboratory, S. (t.t.). Etap Online. http://stdelaboratory.blogspot.co.id/2013/11/tentang-etap-electric-transient-and.html
Luthfiyani, U. K., Setiawan, A., & Arifin, S. (2023). INSOLOGI: Jurnal Sains dan Teknologi Analisis Perbandingan Indeks Keandalan Sistem Jaringan Distribusi dengan Metode Section Technique dan Reliability Index Assessment (RIA): Studi Kasus Gardu Induk Balaraja. Media Cetak, 2(1), 250–264. https://doi.org/10.55123/insologi.v2i1.1782
Maliky, A. T., & Haryudo, S. I. (2020). Keandalan Sistem Distribusi 20 kV Pada Penyulang Pejangkungan Dengan Metode RIA. https://ejournal.unesa.ac.id/index.php/JTE/article/view/30122
PRAYOGI, A. A. (2021). Analisis Keandalan Sistem Distribusi 20 kV pada Penyulang Selapan Jaya dan Penyulang Jahe di PLTBg PT. Sampoerna Agro. JURNAL SURYA ENERGY, 6(1), 25. https://doi.org/10.32502/jse.v6i1.3105
Putri Hesti, L., & Nugraha, A. E. (2023). Analisis Komponen Kritis Mesin Bubut Underfloor Menggunakan Metode Failure Mode and Effect Analysis dan Fault Tree Analysis. VIII(3).
Sanaky, M. R., Sulistiawati, B., Pembimbing, D., & Nurcahyo, I. E. (t.t.). Peningkatan Indeks Keandalan dengan Penambahan Recloser pada Sistem Distribusi di PLTD Subaim Menggunakan Metode Section Technique.
Additional Files
Published
Issue
Section
License
Copyright (c) 2024 Fauzia Haz, Arya Mustopa, Giri Angga Setia, Dede Furqon, Atik Charisma, M. Reza Hidayat

This work is licensed under a Creative Commons Attribution 4.0 International License.
Authors retain copyright and grant Jurnal Teknik: Media Pengembangan Ilmu dan Aplikasi Teknik the right of first publication. Articles are published open access under the Creative Commons Attribution 4.0 International License (CC BY 4.0), which permits use, sharing, adaptation, distribution, and reproduction in any medium or format, for any purpose, provided that appropriate credit is given to the original authors and source, a link to the license is provided, and any changes are indicated.