Diagnosis Kondisi Minyak Tranformator Menggunakan Teknik Dissolved Gas Analysis
DOI:
https://doi.org/10.55893/jt.vol21no1.428Keywords:
Transformer Oil, Dissolved Gas Analysis, Breakdown VoltageAbstract
At the Cikalong hydropower plant there are 3 power transformers with a voltage rating of 6.3/77 kV, because of their long life, it is necessary to analyze the condition of the transformer oil. One way to determine the level of fault gas contained in transformer oil is the DGA (Dissolved Gas Analysis) test. DGA will extract the gas to find out indications of disturbance based on the interpretation of the dissolved gases data, namely the Total Dissolved Combustible Gas (TDCG), Key Gas, Roger's Ratio, Doernenberg's Ratio and Duval's Triangle methods. This method is in order to determine the condition of the transformer oil is normal or not, measure the breakdown voltage value and calculate the correlation value between operating hours and the amount of power production. The results of the DGA analysis on transformer units 1, 2, and 3 of the Cikalong hydropower sub-unit show the TDCG value in condition 1, which includes all transformers in good condition. The value of the correlation coefficient between hours of operation and the number of kWh production with TDCG is 0.267 and 0.297, respectively, which indicates the relationship between these variables is a weak relationship (standard value is close to 1).
References
A Dedi Roi Candra Sihombing, “Analisa Kondisi Minyak Isolasi Transformator Berdasarkan Pengujian DGA Pada Transformator 3 150/20 kV 60 MVA PT. PLN (Persero) Gardu Induk Cibatu” 2020.
A. R. Demmassabu, L. S. Patras, F. Lisi, “Analisis Kegagalan Transformator Daya Berdasarkan Hasil Uji Dengan Metode TDCG, Key Gas, Roger's Ratio, Duval's Triangle Pada Gardu Induk” eJurnal Teknik Elektro dan Komputer, ISSN : 2301-8402. 2014.
Faris Aljiddi, “Analisis Hasil Uji DGA untuk Memprediksi Rentang Waktu Purifikasi Minyak Transformator dengan Metode TDCG dan Roger’s Ratio” 2019.
Haz, F. and Aditya, I. (2020) ‘Analisis Setting Proteksi Relai Arus Lebih dan Relai Gangguan Tanah Pada Transformator Daya 60 MVA di Gardu Induk 150 kV Cibatu’, Journal of Electrical Engineering and Information Technology
Hidayat, M. R. et al. (2020) ‘Analisis Kemampuan Minyak Isolasi Transformator Daya Merek Unindo Dengan Pengujian Dissolved Gas Analysis dan Breakdown Voltage di Gardu Induk Serpong’, EPSILON: Journal of Electrical Engineering and Information, pp. 100–106.Pramono, A., Haddin, M. and Nugroho, D. (2016) ‘Analisis Minyak Transformator Daya Berdasarkan Dissolved Gas Analysis (Dga) Menggunakan Data Mining Dengan Algoritma J48’, Telematika, 9(2), p. 78. doi: 10.35671/telematika.v9i2.457.
IEEE std. C57.104-2008, IEEE Guide for Dissolved Gas Analysis in Transformer. 2008.
P, A. Y. C., Taqiyyudin, M. A. and Basuki, B. M. (2018) ‘Analisis Kegagalan Transformator Berdasarkan Hasil Pengujian Dissolved’.
Rahmat Hardityo, “Deteksi dan Analisis Indikasi Kegagalan Transformator Dengan Metode Analisis Gas Terlarut” 2008.
Suardi Yakub, Modul Panduan Belajar Statistik Probabilitas. 2012.
Syakur, A. and Lazuardi, W. (2019) ‘Penerapan Metode Interpretasi Rasio Roger , Segitiga Duval , Breakdown Test , dan Water Content Test untuk Diagnosis Kelayakan Minyak Transformator’, Teknik, 40(1), pp. 63–68. doi: 10.14710/teknik.v40n1.22056.Iskandar, H. R. (2021) ‘Studi Kelayakan Operasi Berdasarkan Uji Dissolve Gas Analysis pada Transformator Distribusi 150 kV Gardu Induk Cibabat Cimahi’, Kilat, 10(1), pp. 10–21. doi: 10.33322/kilat.v10i1.963.
Additional Files
Published
Issue
Section
License
Copyright (c) 2022 Fauzia Haz, Muhammad Rizki Akbar, Giri Angga Setia

This work is licensed under a Creative Commons Attribution 4.0 International License.
Authors retain copyright and grant Jurnal Teknik: Media Pengembangan Ilmu dan Aplikasi Teknik the right of first publication. Articles are published open access under the Creative Commons Attribution 4.0 International License (CC BY 4.0), which permits use, sharing, adaptation, distribution, and reproduction in any medium or format, for any purpose, provided that appropriate credit is given to the original authors and source, a link to the license is provided, and any changes are indicated.